MODULAR UPS

MODULAR UPS

Maxpower Series 6 kVA UPS is an online double conversion UPS that features a single phase in both input and output, and an output power factor of 0.9. This has a tower type design to be used in workstations and critical equipment.

Product Overview

Maxpower Series 6 kVA UPS is an online double conversion UPS that features a single phase in both input and output, and an output power factor of 0.9. This has a tower type design to be used in workstations and critical equipment.

GENERAL FEATURES
Online double conversion with full digital control

  • Wide input voltage range:110~286Vac
  • Wide input frequency range
  • Input Power factor 0.99 with PFC
  • ECO mode operation for energy saving
  • Cold start
  • Self-testing when UPS start-up
  • Generator compatible
  • Intelligent fan speed regulation
ModelCN7006MPI/CN7006MPE

Capacity

VA

6000

Watts

5400

Input

Normal Voltage220/230/240Vac

Operating Voltage Range

110~286Vac

Operating Frequency Range

40~70Hz (50/60Hz Auto-Sensing)

Power Factor

≥0.99 

Bypass voltage range

Max.voltage:230~264Vac

Min.voltage:176~220Vac

ECO RangeSame as the bypass
Harmonic distortion (THDi)<3%(100% linear load
Generator InputSupport

Output

Rated voltage220/230/240Vac 

Power Factor

0.9

Voltage Regulation

±1%

Freq. Line mode

±10% of the rated frequency

Freq. Bat. mode

50Hz / 60Hz (±0.1)Hz

Crest Factor

3:1

Harmonic Distortion (THDv)

≤2% with linear load, ≤5% with non-linear load

Efficiency

>93.5%

Output WaveformPure Sine Wave

Battery

Battery Voltage

(Standard unit 192Vdc)        192/216/240Vdc (Adjustable)

Capacity (Standard unit)

7Ah/12V (9Ah/12V optional)

Typical recharging Time

6~8 hours (to 90% of full capacity)

Charging current

1.35A(Standard unit); Long run unit Max.current 8A(charging current can be set according to battery capacity installed)

System features

Transfer timeMains to battery: 0ms; Inverter to bypass: 5ms (Typical)

Overload                                            Line mode 

Load≤105% long time running; ≤125% last 10min; ≤130% last 30s; >130% turn to bypass mode immediately

Overload                                         Bypass mode40A(Breaker)

Short circuit

Hold whole system

Overheat

Line mode: Turn to bypass; Backup mode: shut down UPS immediately

Battery lowAlarm and switch off
Self-diagnosticsUpon power on and software control
BatteryAdvanced battery management
Audible & Visual alarmsLine failure, Battery under voltage, Overload, System fault
LED and LCD DisplayLine mode, Bat. mode, Eco mode, Bypass mode, Battery under voltage, Overload & UPS Fault
LCD DisplayInput voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage, Inner temperature & Remaining battery backup time
Communication interfaceRS232, USB,SNMP card(optional), Relay card (optional)

Environment

Operating temperature

0~40°C

Storage temperature

-25~55°C

Humidity range

20~95% (Non-condensing)

Altitude

<1500m

Noise Level<55d

Standards

SafetyIEC/EN62040-1,IEC/EN62477-1

EMC

IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8,IEC61000-4-11,IEC6100-2-2

Physical

DimensionI:191 x 460 x 720                     E:191 x 460 x 337

Net Weight (kg)

69.5                                                         12

Specifications are subject to change without prior notice

EXTERNAL BATTERY PACK 
ModelCNBC06120CT
BATTERY SYSTEM 

Battery Type

VRLA (Valve Regulated Lead Acid Battery – SMF)

Typical battery recharging time6~8 hours (to 90% of full capacity)
Typical Battery Life3~5 years, depend on discharging cycle and ambient temperature

System Voltage

240Vdc

Battery Qty2*20 pcs

Capacity

7Ah/9Ah (12V)

PHYSICAL 
Dimension(WxDxH)250 x 619 x 616
Net weight(kg)122/134
ENVIRONMENT 
Operating environment0°C~40°C
Relative humidity0~95% (Non condensing)
Noise Level<40dB at 1 Meter
Part NumberDescription

CN7006MPI

6kVA Medium Power Transformerless UPS (Internal battery) 

CN7006MPE

6kVA Medium Power Transformerless UPS (External battery) 

CNBC06120CT

240VDC Tower Mount Battery Pack

COMPATIBLE ACCESSORIES

Part NumberDescription
CNS01SNMP Card for 10-80kVA 3/1 and 3/3
EXTERNAL BATTERY PACK 
ModelCNBC06120CT
BATTERY SYSTEM 

Battery Type

VRLA (Valve Regulated Lead Acid Battery – SMF)

Typical battery recharging time6~8 hours (to 90% of full capacity)
Typical Battery Life3~5 years, depend on discharging cycle and ambient temperature

System Voltage

240Vdc

Battery Qty2*20 pcs

Capacity

7Ah/9Ah (12V)

PHYSICAL 
Dimension(WxDxH)250 x 619 x 616
Net weight(kg)122/134
ENVIRONMENT 
Operating environment0°C~40°C
Relative humidity0~95% (Non condensing)
Noise Level<40dB at 1 Meter

                                                                     

Part NumberDescription

CN7006MPI

6kVA Medium Power Transformerless UPS (Internal battery) 

CN7006MPE

6kVA Medium Power Transformerless UPS (External battery) 

CNBC06120CT

240VDC Tower Mount Battery Pack

COMPATIBLE ACCESSORIES

Part NumberDescription
CNS01SNMP Card for 10-80kVA 3/1 and 3/3
Scroll to Top